e-TAITEC.com

Product Info

Large inverter chiller CHV series (Air-cooled separate type)

Cooling pump CHV-3750AS

Code No.:

The air-cooled separate type and ideal for cleanroom. The equipped inverter can save energy and realize high accuracy. It can be customized based on the following specifications upon request.

Picture of CHV-750AS(Indoor unit and Outdoor unit ) ※Plumbing the indoor/chiller unit and the outdoor unit required.

Applications

The temperature control for Transmission electron microscope.

Down Load(Useful Information)

TAITEC general catalog - Large inverter chiller CHV series(Air-cooled seperate type) CHV-750AS~6000AS (PDF)

Features


 
The separate type is ideal for temperature control for precision equipment with no exhaust heat in the room.
(*The chiller unit and the outdoor unit are not placed side by side as shown in the figure, in fact, they installed separately.)
The equipped inverter can save energy and realize low operation noise and small consumption current.
Saves energy up to Max. 60% (※Compared with our conventional products) of operating current and Realizes high accuracy of ± 0.1℃.
Customizable upon request as a special order.
Can be customized based on the following specifications upon request. Please feel free to ask us. Cooling capacities other than the notation and precision temperature control ± 0.05℃ are available as an option
Equipped with Warning indicator lamp.
Failure diagnosis can be performed quickly to shorten the time required for recovery.
Restrains the generation of green copper rust to reduce defect.
Restrains the generation of green copper rust to reduce defect.

Specifications

ModelCHV-3750AS
Temperature range+10℃ to +25℃
Control accuracy (*1)±0.1℃
Cooling capacity[kW](Circulation temperature at 10℃)(*2)18
Compressor output, Refrigerant3.75kW, R410A
Pumping capacity(50/60kHz)(*3)Max. discharge pressure[MPa]:0.59
Flow rate[L/min]: 42/55
Motor output[kW]:0.75
Safety device/functionShort/Over current breaker, Warning and Cut off for low water, Pump overcurrent, Water temperature abnormal, Warning indicator lamp
Water bath capacity(at 80% water level)110L
Connecting pipe diameter (Circulating fluid in/out) Rc1-1/4
External dimensionsIndoor unit([W×D×Hmm]: 570×677×1241
Outdoor unit[W×D×Hmm]: 900×320×1540
WeightIndoor unit: 125kg
Outdoor unit: 116kg
Power Supply (three phase AC200V, 50/60Hz) (*4)50A
Operation current30A
(*1) Performance may not be maintained due to environmental temperature, heat load, circulation pipe distance, etc. When the thermal load becomes below approx. 30% of the cooling capacity, the control accuracy changes to ± 2.0℃ due to the compressor On-Off control.
(*2) Capacity when the ambient temperature at below +30℃.
(*3) Capacity when using tap water. Flow rate when the discharge pressure at 0.3 MPa.
(*4) The sensitivity current in ELCB should be set larger than 30 mA.
●•The cooling capacity may not be maintained if the unit is placed in direct sunlight and hindrance of exhausting..
●There is a distance limit between the indoor unit and out door unit, so please contact us for more information.
●Pure water is available as an option
●Please ask us when mixing chemicals for water treatment to circulating fluid.
●The fee for Delivery, Installing, Piping work, and Wiring work are quoted separately.

Related Products

Large inverter chiller CHV series (Air-cooled separate type) | Cooling pump | CHV-750AS
The air-cooled separate type and ideal for cleanroom. The equipped inverter can save energy and realize high accuracy. It can be customized based on the following specifications upon request.
■Temperature range:+10℃ to +25℃ ■Control accuracy (*1):±0.1℃
Large inverter chiller CHV series (Air-cooled separate type) | Cooling pump | CHV-1500AS
•The air-cooled separate type and no noise or vibration in the room •The equipped inverter can save energy and realize high accuracy •Plumbing for the indoor unit and the outdoor unit is required
■Temperature range:+10℃ to+25℃ ■Control accuracy (*1):±0.1℃
Large inverter chiller CHV series (Air-cooled separate type) | Cooling pump | CHV-2200AS
The air-cooled separate type and ideal for cleanroom. The equipped inverter can save energy and realize high accuracy. It can be customized based on the following specifications upon request.
■Temperature range:+10℃ to+25℃ ■Control accuracy (*1):±0.1℃
Large inverter chiller CHV series (Air-cooled separate type) | Cooling pump | CHV-4500AS
The air-cooled separate type and ideal for cleanroom. The equipped inverter can save energy and realize high accuracy. It can be customized based on the following specifications upon request.
■Temperature range:+10℃ to+25℃ ■Control accuracy (*1):±0.1℃
Large inverter chiller CHV series (Air-cooled separate type) | Cooling pump | CHV-6000AS
The air-cooled separate type and ideal for cleanroom. The equipped inverter can save energy and realize high accuracy. It can be customized based on the following specifications upon request.
■Temperature range:+10℃ to +25℃ ■Control accuracy (*1):±0.1℃